DC6: a water-based coolant with very little glycol

DC6 is a ready-to-use, water-based coolant for direct-to-chip loops, formulated and made in-house. It contains less than 5% antifreeze, so it conducts heat better than a PG25 and flows more easily. The trade-off is less freeze protection.

Request DC6 information
Antifreeze content
Less than 5%
Freeze point
About −4 °C
Boiling point
About 102 °C
pH
About 8.5

How DC6 compares with PG25

Choose DC6 when the loop stays above freezing and you want the thermal and pumping benefits of less glycol.

At 40 °C: Thermal conductivity, W/(m·K)DC60.514MatScienceAI PG250.488
At 40 °C: Dynamic viscosity, mPa·sDC61.28MatScienceAI PG251.40
At 40 °C: Specific heat, kJ/(kg·K)DC63.89MatScienceAI PG253.93
At 40 °C: Density, g/cm³DC61.004MatScienceAI PG251.018
At 40 °C: Freeze pointDC6About −4 °CMatScienceAI PG25About −11 °C

DC6 values were measured to ASTM D7896, D445 and D5931. The two fluids were not measured side by side.

What we've measured

  • Physical properties

    Density, thermal conductivity, specific heat and viscosity were measured at nine temperatures from 20 °C to 60 °C. Thermal conductivity rose from 0.486 to 0.531 W/(m·K) across that range.

  • Seals and plastics

    Nine materials stayed within the test limits after 168 hours: EPDM, FKM, silicone and fluorosilicone rubber at 100 °C, and PTFE, PE, PPS, PP and PPA at 70 °C.

Before you choose DC6

  • It freezes at about −4 °C, so it doesn't suit loops that can see lower temperatures, including during shipping or storage.
  • It isn't a PG25, so the Open Compute Project's PG25 guidelines don't apply to it. Check it against your equipment maker's fluid requirements.

Request DC6 information

Tell us about your loop — we'll get back to you within 1–2 business days. Full test data is available under NDA.