Products / DC6 / Available
DC6: a water-based coolant with very little glycol
DC6 is a ready-to-use, water-based coolant for direct-to-chip loops, formulated and made in-house. It contains less than 5% antifreeze, so it conducts heat better than a PG25 and flows more easily. The trade-off is less freeze protection.
Request DC6 information- Antifreeze content
- Less than 5%
- Freeze point
- About −4 °C
- Boiling point
- About 102 °C
- pH
- About 8.5
How DC6 compares with PG25
Choose DC6 when the loop stays above freezing and you want the thermal and pumping benefits of less glycol.
| At 40 °C | DC6 | MatScienceAI PG25 |
|---|---|---|
| At 40 °C: Thermal conductivity, W/(m·K) | DC60.514 | MatScienceAI PG250.488 |
| At 40 °C: Dynamic viscosity, mPa·s | DC61.28 | MatScienceAI PG251.40 |
| At 40 °C: Specific heat, kJ/(kg·K) | DC63.89 | MatScienceAI PG253.93 |
| At 40 °C: Density, g/cm³ | DC61.004 | MatScienceAI PG251.018 |
| At 40 °C: Freeze point | DC6About −4 °C | MatScienceAI PG25About −11 °C |
DC6 values were measured to ASTM D7896, D445 and D5931. The two fluids were not measured side by side.
What we've measured
Physical properties
Density, thermal conductivity, specific heat and viscosity were measured at nine temperatures from 20 °C to 60 °C. Thermal conductivity rose from 0.486 to 0.531 W/(m·K) across that range.
Seals and plastics
Nine materials stayed within the test limits after 168 hours: EPDM, FKM, silicone and fluorosilicone rubber at 100 °C, and PTFE, PE, PPS, PP and PPA at 70 °C.
Before you choose DC6
- It freezes at about −4 °C, so it doesn't suit loops that can see lower temperatures, including during shipping or storage.
- It isn't a PG25, so the Open Compute Project's PG25 guidelines don't apply to it. Check it against your equipment maker's fluid requirements.
Request DC6 information
Tell us about your loop — we'll get back to you within 1–2 business days. Full test data is available under NDA.
sales@matscienceai.com