OCP PG25 guidelines vs the Base Specification: what each requires

MatScienceAI · November 12, 2026 · 13 min read

Short answer

OCP's PG25 Base Specification v1.0.0 (14 July 2026) sets requirements on fluid manufacturers for a new, ready-to-use fluid. The PG25 Guidelines Rev 2.0 (15 September 2026) is an operator-facing white paper of recommended practice and in-use limits. Most numbers agree. pH windows, reserve alkalinity, the 24% versus 25% glycol floor and hardness do not. Put the Base Specification in purchase specs and run the loop on Rev 2.0 with supplier-specific limits.

Two OCP documents now cover PG25 in cold plate loops, and they answer different questions. The Base Specification for Single-Phase Propylene Glycol-Based Cold Plate Coolants (PG 25), v1.0.0, dated 14 July 2026, tells fluid manufacturers what their product must be when it leaves the plant [2]. The Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Revision 2.0, dated 15 September 2026, tells the people who design, fill and run a technology cooling system (TCS) how to look after the fluid once it is in the loop [1].

Most of their numbers line up. Four do not, and one of them only shows up when you do the arithmetic. We read both documents end to end, along with the 2022 guidelines that Rev 2.0 updates [3], and put every numeric limit side by side.

The Base Specification sets supplier requirements; Rev 2.0 advises operators

The Base Specification's scope says it is intended for PG25 suppliers and sets requirements on manufacturers [2]. Almost every clause is a requirement on the supplier, and its section 10 lists what a supplier has to meet to call a fluid compliant [2]. Rev 2.0 names design engineers, facility operators and data center staff as its primary audience, and says that instead of rigid requirements it offers "a baseline framework of recommended practices" [1]. Its table of new-fluid properties carries a footnote saying the values are representative and are not specifications [1].

OCP's catalogue reflects the split. On the Cooling Environments contribution list, the Base Specification sits in the Cold Plate family and the Guidelines sit in the Information family [4]. The two kinds of document are approved differently: a specification needs a majority vote of the OCP Steering Committee followed by a 30-day opt-out period (which can be waived), while a document or white paper gets a two-week Steering Committee review before publication [5]; Rev 2.0 was built on OCP's white paper and document submission template [1]. OCP describes a base specification as "an architectural framework for coarse alignment" that more detailed design and product specifications can build on [6].

Both documents carry as-is disclaimers of warranty. The Base Specification's scope addresses it to PG25 suppliers, and every compliance item in its section 10 is a supplier obligation; Rev 2.0 presents itself as recommended practice, though a few of its lines are phrased as requirements, for example that flush water meet its Table 12 [1][2]. Of the two, the Base Specification is the one that suits a purchase specification as pass/fail, because it is written as supplier requirements. Rev 2.0 is what you build operating procedures around, adjusted to your supplier's fluid-specific limits, which Rev 2.0 itself says may vary slightly from its tables [1].

A naming trap if you go looking for the Guidelines PDF: its title page reads Revision 2.0, Version 1.0.0 and the file name ends in V1.0.0 [1], while OCP's contribution list labels the same file V2.0.0 [4]. They are one document. The Base Specification predates it: it still cites the 2022 guidelines and notes that they were under revision as of 14 July 2026 [2].

Every numeric limit, side by side

The table compares the Base Specification's requirements for new fluid, Rev 2.0's typical values for new fluid (its Table 1), Rev 2.0's in-use limits (Table 14) and the 2022 in-use limits [1][2][3]. Concentrations are in ppm unless marked.

Parameter Base Spec v1.0.0, new fluid (must) [2] Rev 2.0 Table 1, new fluid (typical) [1] Rev 2.0 Table 14, in use [1] 2022 guidelines, in use [3]
Propylene glycol 25-28 wt% (about 24.5-27.5 vol%) 24.5-27.5 vol% 24-29 vol% 24.5-29.5 vol%
pH 7.5-10.5 8.0-10.5 non-OAT; 7.0-10.5 OAT 8.0-10.5 IAT; 6.5-9.5 OAT or hybrid 8.0-10.5
Reserve alkalinity, ASTM D1121 No limit set >6 mL conventional; report only for OAT >4 mL conventional; report only for OAT >4 mL
Copper <2 Not listed <3 (monitor more often above 5) <2
Iron <2 Not listed <3 (monitor more often above 5) <2
Aluminum <2 Not listed Not listed Not listed
Chloride <5 <5 <25 (consult supplier above 50) <25
Sulfate <10 <10 <25 (consult supplier above 100) <25
Hardness Ca <5, Mg <10 Total <25 as CaCO3 Total <50 as CaCO3 Total <100 as CaCO3
Silicon <10 Not listed Not listed Not listed
Modified ASTM D8040 weight loss Copper and brass 5 mg; 304/304L and 316/316L 2 mg Same, via its Table 10 Not applicable 2022 new-fluid criteria: copper 5 mg, brass 10 mg
Modified ASTM D7437 hard-water stability <0.25 mL precipitate Not covered Not covered Not covered

Many of the gaps between columns are deliberate. Rev 2.0 says new-fluid and in-use criteria differ because system materials, commissioning residue, maintenance and normal aging change the fluid, and that its in-use values are for spotting abnormal conditions, not for demanding a return to new-fluid properties [1]. Four differences are worth a closer look.

Four places where the documents pull apart

pH: one window for new fluid, two for fluid in service

The Base Specification gives every PG25 fluid the same window, 7.5 to 10.5 in the ready-to-use state [2]. Rev 2.0 splits by inhibitor chemistry: its typical range for new OAT fluids starts at 7.0, and for OAT or hybrid fluids in service the window is 6.5 to 9.5 [1].

On paper that allows two awkward cases. A new OAT fluid at pH 7.2 sits inside Rev 2.0's typical range and outside the Base Specification. A new OAT fluid at pH 10.0 is Base-compliant, and inside Rev 2.0's own new-fluid typical range, yet above Rev 2.0's in-use ceiling of 9.5 before it has circulated once. We do not know whether any commercial fluid sits at either edge. Formulations are proprietary, and the Base Specification lets them stay that way [2]. The fix is to ask your supplier, in writing, which in-use pH window applies to its fluid, since Rev 2.0 says its ranges may vary slightly with supplier guidance [1].

Reserve alkalinity is a Rev 2.0 limit, not a Base Specification one

The Base Specification requires the laboratories the manufacturer runs or approves to be able to measure reserve alkalinity by ASTM D1121, but we found no minimum anywhere in it [2]. Rev 2.0 gives typical new-fluid values above 6 mL and an in-use limit above 4 mL, both for conventional inhibitor technology; for OAT fluids it asks only that the value be reported [1]. A low reserve alkalinity on a certificate of analysis is therefore not a Base Specification failure in itself. Whether it matters depends on the inhibitor type, and that is a question for the supplier.

The glycol floor: 25% or 24%?

Section 9.1 of the Base Specification requires the original manufacturer to offer a concentrated fluid, such as PG50 or PG55 with the same additive package, for restoring glycol when concentration falls below 25% [2]. It does not say whether that 25% is by weight or by volume. Rev 2.0's in-use table sets the action point at 24% by volume, and its remediation table repeats 24% [1]. Elsewhere Rev 2.0 says bio-growth may occur if concentration is not kept at about 25% or above, and its in-line sensor table talks about keeping the fluid above 25% [1].

So a loop at 24.5% by volume is inside Rev 2.0's in-use range and, if the Base Specification's trigger is read as volume percent, below it. Read as weight percent, the gap mostly closes: the 2022 guidelines say weight percent runs about 0.5 to 1.0% above volume percent, which we read as percentage points [3], which puts 24.5 vol% at roughly 25.0-25.5 wt%. Agree the basis with your supplier before the first refractometer reading, and use the supplier's own refractive index table, since both documents say inhibitors shift refractive index and a fluid-specific table is needed [1][2].

For scale, take a 1,000 L loop that has drifted to 22.5%, the figure our PG25 mixing article calculated for a changeover with two water flushes. To reach 25% by draining x litres and replacing them with PG55: (1,000 - x) × 0.225 + 0.55x = 250, so x = 25 / 0.325, about 77 L. That treats volume percentages as additive, which is an approximation. Rev 2.0 says to get the calculation from the fluid vendor, with the system volume known [1].

Hardness: a fluid at the Base Specification's limits would exceed Rev 2.0's in-use limit

The Base Specification limits calcium to under 5 ppm and magnesium to under 10 ppm, and notes that small amounts of these cations are a common way to stabilize phosphate, together with an anionic polymer [2]. Rev 2.0 states hardness as total hardness as CaCO3: typically under 25 ppm in new fluid, and under 50 ppm in use, with a call to the supplier above 50 [1].

The standard conversion, as given by the US EPA, is hardness as CaCO3 = 2.497 × Ca + 4.118 × Mg, stated in mg/L [7]. We treat ppm as mg/L here; strictly the two differ by the fluid's density, which is on the supplier's data sheet. At the Base Specification's ceilings:

2.497 × 5 + 4.118 × 10 = 12.5 + 41.2 = 53.7 ppm as CaCO3

That is above Rev 2.0's typical new-fluid value of 25 and above its in-use limit of 50 [1]. Magnesium does most of the work: 10 ppm of Mg alone is 41.2 ppm as CaCO3. A fluid at both ceilings is a theoretical worst case, and we have no data showing any product near it. Still, if a certificate or baseline lab report gives calcium and magnesium separately, convert before comparing with Rev 2.0, and do not assume a Base-compliant number is inside the operating table. The same check on the Base Specification's blending-water limits (Ca <2, Mg <2 ppm) gives 13.2 ppm, inside its own total-hardness limit of 15 ppm [2].

The corrosion limits agree, and the mg and mpy figures nearly do

Both 2026 documents use the same modified ASTM D8040 test: ready-to-use fluid without further dilution, corrosive salts added, 88 °C for two weeks with continuous aeration, in triplicate, with maximum weight losses of 5 mg for copper and brass and 2 mg for 304/304L and 316/316L stainless steel (304L and 316L in Rev 2.0) [1][2]. Rev 2.0 describes the unmodified method as diluting concentrated fluid to 30% by volume [1], where the 2022 guidelines described it as 30% by weight [3]. We could not check the ASTM text, which is paywalled. The public summary of D8040 says its results "cannot stand alone as evidence of satisfactory corrosion inhibition" [8], and Rev 2.0 calls it a screening tool [1].

Both documents also quote a corrosion rate in mils per year (mpy): 0.2 mpy for copper and brass, 0.1 mpy for stainless steel [1][2]. The Base Specification labels these as estimated rates based on standard 1/16 × 2 × 1 inch coupons [2]. OCP's water-based coolant base specification gives the conversion: mpy = (weight loss in g × 22,300) / (area in in² × density in g/cm³ × time in days) [9]. Checking the PG25 figures over 14 days:

Metal Density, g/cm³ Weight-loss limit Calculated rate Stated rate [1][2]
Copper C11000 8.9 [10] 5 mg 0.005 × 22,300 / (4.375 × 8.9 × 14) = 0.20 mpy 0.2 mpy
Brass C26000 8.53 [11] 5 mg 0.005 × 22,300 / (4.375 × 8.53 × 14) = 0.21 mpy 0.2 mpy
Stainless 304L 8.03 [12] 2 mg 0.002 × 22,300 / (4.375 × 8.03 × 14) = 0.09 mpy 0.1 mpy

The 4.375 in² is the coupon's surface area, 2(2 × 1) + 2(2 × 0.0625) + 2(1 × 0.0625), with the mounting hole ignored. The mass limits and the mpy labels agree to within rounding. For brass, 5 mg comes out just above 0.2 mpy, so if a lab report gives both, read the mass: it is what the coupon measures, and the Base Specification calls the mpy figure an estimate [2]. Rev 2.0 adds that the test cannot tell 0.1 mpy from 0.2 mpy for copper, so 5 mg per coupon is about the limit of what it can discriminate [1].

The same formula clarifies a change from 2022. The 2022 guidelines listed copper at 0.22 mpy (5 mg) and brass at 0.46 mpy (10 mg) [3]. At these densities, both pairs imply a coupon area of about 4.06 in², so the 2022 figures appear to rest on a different area or density assumption, which the document does not state. The copper limit in milligrams has not changed. Brass tightened from 10 mg to 5 mg, and stainless steel, which the 2022 test left out (it asked only for copper and brass coupons), now has a 2 mg limit [1][3].

Four water tables, four different jobs

Three of the documents discussed here set four water-quality tables between them, and the limits differ. (The 2022 guidelines had their own flush and dilution water limits, with a total-hardness ceiling of 50 ppm [3].)

Parameter Blending water, Base Spec Table 1 [2] Dilution water, Rev 2.0 Appendix 1 [1] Flush water, Rev 2.0 Table 12 [1] Procedure water, TCS manifold guidelines Table 5 [13]
Chloride, ppm <10 <10 <25 Not listed
Sulfate, ppm <10 <10 <25 Not listed
Total hardness as CaCO3, ppm <15 (Ca <2, Mg <2) <15 (Ca <2, Mg <2) <25 Not listed
Iron, ppm <2 <2 <2 Not listed
pH 5-8 5-8 5-8 6 minimum
Conductivity, µS/cm <25 at 20 °C <25 at 20 °C <25 50 maximum
Bacteria, CFU/mL <100 <100 <100 1,000 maximum
Turbidity Not listed Not listed <1 NTU Not listed

Rev 2.0 says the differences are intentional: the manifold guidelines favor parameters that can be checked in the field, while its own flush-water table aims to keep contaminants out of the PG25 and can be stricter [1]. Two practical readings follow. Water used to dilute PG25 in service has to meet the same limits as the water the manufacturer blends with. And water that passes the manifold pre-commissioning table can still fail Rev 2.0's flush-water table on conductivity (50 against 25 µS/cm) and bacteria (1,000 against 100 CFU/mL). If one contractor handles both stages, hand over both tables.

What else Rev 2.0 changed from the 2022 guidelines

Beyond the limits in the first table, Rev 2.0 rewrites several operating instructions [1][3].

Topic 2022 guidelines [3] Rev 2.0 [1]
Lab analysis Annual, if deemed necessary; on-site testing quarterly Each loop should be lab-tested at least annually; risk-based schedule, up to quarterly for the first 1.5 years in the high-risk case
Fluid life A five-year life could be achieved within the guidelines No figure; replace per supplier recommendation, and suppliers typically do not guarantee life (as in 2022)
Filtration Sidestream below 5 µm on 10% of flow Does not prescribe type, size or efficiency; sidestream typically 5-15% of flow; 5-10 µm absolute recommended during fill
Flushing Fixed sequences. New systems: one 30-minute flush with the heat transfer fluid, then drain. Existing systems: two 30-minute water flushes, then a heat transfer fluid rinse Flush until cleanliness targets are met; uninhibited water only for early flushing and out within 24 hours
Materials Metals list; elastomers, plastics and other materials list Adds filter media, recommends peroxide-cured EPDM, lists polyamide 11 and 12 as under evaluation
Another fluid in new equipment Covers changing fluid in existing systems only Flush and fill with the operating fluid before connection

How we would use the two documents

In a fluid purchase specification, cite the Base Specification by version and date, v1.0.0 of 14 July 2026, and ask for what it obliges the supplier to provide. That means a certificate of analysis with, or available at, every delivery, giving glycol concentration (or refractive index with its measurement temperature) and pH with its measurement temperature; a technical data sheet with viscosity, heat capacity, density and thermal conductivity measured on the final product across the operating range; batch retains kept for at least six months and batch records for five years; and a matching concentrate and re-inhibiting additive package [2]. Ask for the modified D8040 and D7437 results too. Then add what the Base Specification leaves open: the inhibitor type (IAT, OAT or hybrid), the supplier's in-use pH and reserve alkalinity limits, and whether its 25% trigger is weight or volume.

For operations, start from Rev 2.0's Table 13 sampling schedule and Table 14 limits, swap the generic pH and reserve alkalinity rows for the supplier's fluid-specific values, and convert any separate calcium and magnesium results to total hardness before comparing [1][7]. Keep the 2022 guidelines out of new procedures. Rev 2.0's version history lists it as a full update of the 2022 document [1], and the old in-use limits differ in both directions: hardness was looser, copper and iron tighter.

Neither document says two compliant fluids are interchangeable. The Base Specification says compliance "does not imply" it [2], which is why a supplier change should be planned as a flush and fill.

Frequently asked questions

Is the OCP PG25 Base Specification mandatory?

It sets requirements for PG25 suppliers who want to call a fluid compliant with it; its scope is addressed to suppliers, and how a buyer uses it depends on the purchase contract, so check with your procurement or legal team. OCP files it as a base specification, which goes through a Steering Committee vote, while the Rev 2.0 Guidelines are filed as an information document.

Which pH range applies to PG25: 7.5-10.5 or 8.0-10.5?

Both, at different stages. The Base Specification requires a new ready-to-use fluid to sit between 7.5 and 10.5. Rev 2.0 uses 8.0-10.5 for conventional (IAT) fluids in service and 6.5-9.5 for OAT or hybrid fluids, and says these ranges may vary slightly with supplier guidance. Ask your supplier for the in-use window for its specific fluid.

Which version of the OCP PG25 guidelines is current?

Revision 2.0, dated 15 September 2026. The PDF's title page says Revision 2.0, Version 1.0.0 and the file name ends in V1.0.0, while OCP's contribution list labels the same file V2.0.0. Its version history lists it as a full update of the 2022 guidelines. The 2022 in-use hardness limit was looser (<100 against <50 ppm), its copper and iron limits were tighter (<2 against <3 ppm), and its new-fluid brass corrosion criterion allowed 10 mg against 5 mg now.

Does the Base Specification mean two PG25 fluids can be mixed?

No. The Base Specification states that compliance does not imply that PG25 fluids from different suppliers are interchangeable or functionally equivalent, and it leaves inhibitor packages proprietary. Rev 2.0 says equipment holding a different PG25 formulation should be flushed and filled with the operating fluid.

References

  1. Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Revision 2.0, Version 1.0.0. Open Compute Project, 2026-09-15. https://www.opencompute.org/wp-content/uploads/2026/10/OCP-PG25-Guidelines-V1.0.0.pdf
  2. Base Specification for Single-Phase Propylene Glycol-Based Cold Plate Coolants (PG 25), Version 1.0.0. Open Compute Project, 2026-07-14. https://www.opencompute.org/documents/ocp-base-specification-pg25-v1-0-0-final-pdf/
  3. Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Single-Phase Cold Plate-Based Liquid Cooled Racks (2022 version). Open Compute Project, 2022. https://www.opencompute.org/documents/guidelines-for-using-propylene-glycol-based-heat-transfer-fluids-in-single-phase-cold-plate-based-liquid-cooled-racks-final-pdf/
  4. Contributions Archive (Cooling Environments filter). Open Compute Project, accessed 2026-11-12. https://www.opencompute.org/contributions/?project=Cooling%20Environments
  5. How to Contribute. Open Compute Project, accessed 2026-11-12. https://opencompute.org/contributions/how-to-contribute
  6. Evolving OCP Contribution Process. Open Compute Project (Michael Schill), 2023-01-10. https://www.opencompute.org/news/evolving-ocp-contribution-process/
  7. Multi-Sector General Permit, Appendix J: Calculating Hardness in Freshwater Receiving Waters for Hardness Dependent Metals. US Environmental Protection Agency, 2015. https://www.epa.gov/sites/production/files/2015-10/documents/msgp2015_appendixj.pdf
  8. ASTM D8040-18(2023), Standard Test Method for Corrosion Test for Heat Transfer Fluids in Glassware (preview). ASTM International, via iTeh Standards, 2023. https://standards.iteh.ai/catalog/standards/astm/5de8c9e5-be6a-438b-898b-96231a50d07e/astm-d8040-182023
  9. Base Specification for Single Phase Water-Based Cold Plate Coolants, Version 1.3. Open Compute Project, 2026-08-06. https://www.opencompute.org/documents/base-specification-for-single-phase-water-based-cold-plate-coolant-v1-3-final-pdf/
  10. Technical Datasheet C11000 (Cu-ETP). Aurubis, undated, accessed 2026-11-12. https://aurubis.com/dam/jcr:ec116d17-1541-419a-a897-ad31b4fa6c93/c11000-cu-etp-us.pdf
  11. C26000 Cartridge Brass (physical properties provided by CDA). Wieland Concast, accessed 2026-11-12. https://www.concast.com/c26000.php
  12. 304/304L Stainless Steel Product Data Bulletin. Cleveland-Cliffs, 2021. https://d1io3yog0oux5.cloudfront.net/_7ce3a04c09e74bf31ff5f89fc888db25/clevelandcliffs/db/1190/10510/file/CLF_ProductData_304-304LSS_052021.pdf
  13. Guidelines for Pre-Commission Preparation of Technology Cooling System (TCS) Row Manifolds in Liquid Cooled Data Centers. Open Compute Project, 2025. https://www.opencompute.org/documents/ocp-document-submission-guidelines-for-pre-commission-preparation-of-technology-cooling-system-tcs-row-manifolds-revq-pdf-1