Can you mix PG25 coolants from different suppliers?
MatScienceAI · November 4, 2026 · 10 min read
Short answer
Not as routine practice. OCP's PG25 Guidelines Rev 2.0 (September 2026) say equipment holding a different PG25 formulation should be flushed and filled with the operating fluid, and the July 2026 Base Specification says compliant fluids are not necessarily interchangeable. The only public mixing study we found, by GIGABYTE and Castrol, kept all four blends physically stable, but one 50:50 blend exceeded its aluminum corrosion limit. Plan a brand change as a flush and fill.
The short version: OCP tells you to avoid it. Section 11.2 of the PG25 Guidelines Rev 2.0, dated 15 September 2026, recommends using the same heat transfer fluid through design, manufacturing, testing and cleaning, and says that if equipment arrives holding another fluid, including a different PG25 formulation, you should flush and fill it with the operating fluid before it joins the loop, following a protocol from the fluid supplier [1]. A data center technology cooling system (TCS) is a closed loop, typically with copper cold plates and stainless steel piping [1], and the documents written for it are the ones that count.
That does not mean every accidental blend is a disaster. In the only public mixing study we could find, all four blends stayed physically stable and all but one corrosion result met the paper's acceptance values. The exception, one 50:50 blend that lost 84 mg of aluminum against the paper's 60 mg limit, is the point: you cannot tell in advance which pair is the bad one.
PG25 names a concentration, and the inhibitor package is proprietary
"PG25" tells you the glycol content, about 25% propylene glycol by volume [2], and nothing about the corrosion inhibitors that do the protective work. OCP's Base Specification v1.0.0 (14 July 2026) requires 25-28% propylene glycol by weight (about 24.5-27.5% by volume), a pH between 7.5 and 10.5, limits on impurities and a modified ASTM D8040 corrosion result [2]. It explicitly does not standardize inhibitor packages or additive chemistries, lets each supplier keep its additives confidential, and states that compliance "does not imply" fluids from different suppliers are interchangeable [2].
Rev 2.0 makes the same point through its numbers. Its in-use pH window is 8.0-10.5 for conventional (IAT) inhibitor technology and 6.5-9.5 for OAT or hybrid technology, and its reserve alkalinity limit of more than 4 mL applies only to conventional fluids; for OAT fluids the value is "to report" [1]. Blend an IAT fluid with an OAT fluid and you no longer know which set of limits applies to the mixture.
There is also a specific chemical reason to be careful. The Base Specification says amines are not recommended because they can react with nitrite to form nitrosamine, and that amines may be acceptable if nitrites are not present [2]. Read literally, the clause does not stop one compliant fluid from containing nitrite and another, nitrite-free, from containing amines. Mixing those two would create the very combination the clause warns about. We do not know whether any current pair of commercial fluids fits that description, because the formulations are not public, and that is exactly why OCP sends you back to the supplier.
What each source says about mixing, side by side
We read every public document we could find that addresses the question for data center PG25.
| Document | Date | What it says about mixing or changing fluids |
|---|---|---|
| OCP PG25 Guidelines, 2022 version [3] | 2022 | For existing systems, clean and flush before charging with a new fluid, "especially" if the old fluid is incompatible, and warns that incompatible fluids will likely need additional action. Gives a sequence: drain, two water flushes of 30 minutes each, a rinse with the new fluid, drain, fill. Confirm the procedure with the fluid supplier. |
| OCP PG25 Base Specification v1.0.0 [2] | 14 Jul 2026 | Compliance does not imply interchangeability. Inhibitor packages stay proprietary. |
| OCP PG25 Guidelines Rev 2.0 [1] | 15 Sep 2026 | Use one fluid through design, manufacturing, testing and cleaning. Equipment holding water or an alternative PG25 formulation should be flushed and filled with the operating fluid. Restore inhibitors only with additives approved by the original supplier. |
| OCP PG25 Mixing workstream [4] | page read 4 Nov 2026 | Exists under the Cold Plate sub-project. Scope "will be added in the near future". No deliverables listed. |
| GIGABYTE and Castrol whitepaper [5] | undated | Lab and loop tests of Castrol's PG25 blended with three commercial PG coolants. Validation covers only Castrol's fluid as supplied; GIGABYTE does not extend it, or any coolant warranty, to a fluid a customer substitutes. |
No OCP document we read endorses routine mixing. The only document that presents mixing favorably is a joint paper from a server maker and one fluid supplier, and even it disclaims the substituted fluid.
The GIGABYTE and Castrol study, read against OCP's limits
The whitepaper is the only public mixing dataset we found, so it deserves a close reading [5]. Castrol's PG25 was blended with three commercial propylene glycol coolants that the paper identifies only by short labels: one at 50:50 and at 10:90 (10% in-service fluid, 90% Castrol, which the paper calls a realistic changeover), and two others at 50:50. The mixtures were tested for physical properties, glassware corrosion (ASTM D1384), simulated service corrosion (ASTM D2570), and elastomer and plastic aging at 88 °C for 336 hours. The 10:90 blend then ran for 12 weeks in a loop with six thermal test vehicles at about 45 °C inlet and 55 °C outlet.
Here are its reported results next to the OCP Rev 2.0 limits for in-use fluid [1].
| Parameter | Mixtures in the whitepaper [5] | OCP Rev 2.0 in-use limit [1] | Reading |
|---|---|---|---|
| pH (ASTM D1287) | 8.61-8.87 | 8.0-10.5 (IAT); 6.5-9.5 (OAT or hybrid) | Inside both windows |
| Freezing point (ASTM D1177) | -11.6 to -12.1 °C | 24-29% PG gives about -13 to -9 °C | Inside the freeze range OCP gives for 24-29% PG |
| Reserve alkalinity (ASTM D1121) | 2.8, 2.8, 5.1, 4.2 mL | >4 mL for conventional fluids; "to report" for OAT | Two blends below 4 mL. Inhibitor types are not stated, so the limit may not apply |
| Copper and iron after 12-week loop | <1 ppm each | <3 ppm each | Inside |
| Chloride and sulfate after 12-week loop | <5 ppm each | <25 ppm each | Inside |
| Aluminum weight loss, ASTM D2570, one 50:50 blend | 84 mg | No OCP limit; aluminum is not on OCP's representative list of commonly used metals | Exceeds the paper's own 60 mg acceptance value |
Three things stand out.
First, a mixture failed. One 50:50 blend lost 84 mg of aluminum in the simulated service test against the 60 mg acceptance value the paper itself lists. The authors note that GIGABYTE's loops avoid wetted aluminum. That is a fair design answer for their hardware. It does not tell you about a loop elsewhere that has an aluminum part, and OCP's Rev 2.0 metals table does not list aluminum, although OCP describes that table as representative and not comprehensive [1].
Second, the corrosion numbers cannot be read straight across to OCP's limits. OCP's qualification test is ASTM D8040 run on the ready-to-use fluid without further dilution, with corrosive salts added, at 88 °C for 336 hours, and it sets maximum weight losses of 5 mg for copper and brass and 2 mg for 304L and 316L stainless [1][2]. The whitepaper used ASTM D1384 and D2570, which are engine coolant methods. D1384 runs 336 hours at 88 °C, but its standard procedure dilutes the coolant to 33⅓% by volume in corrosive water [6]; the whitepaper does not say whether its PG25 blends were tested as-is or diluted. D2570 (2010 edition) circulates coolant for 1,064 hours at 88 °C through automotive radiator hardware [7]. Copper and brass losses in the glassware test were 0-1 mg, on a different method, so they are not directly comparable with OCP's 5 mg limit. The tables also list "steel" without a grade, so they say nothing about the 304L and 316L limits. Both D1384 and D8040 state that their results cannot stand alone as evidence of satisfactory corrosion inhibition [6][8].
Third, the scope is narrow. The paper shows no unmixed control alongside the blends, so you cannot separate the effect of mixing from the baseline behavior of each fluid. Elastomer and plastic data cover only the 10:90 blend; in that set, polyamide 12 gained 8.1% mass and lost 23.8% tensile strength, and FKM lost 24% tensile strength. OCP Rev 2.0 lists polyamide 12 as a material still under evaluation [1]. The 12-week loop ran only the 10:90 blend, and twelve weeks says nothing about how a blend behaves over years of service.
Our reading: the study is useful evidence that some blends with one fluid behave well on the bench. It is evidence for those pairs only. The paper's own disclaimer says as much.
Worked example: how much old fluid survives a changeover
The practical question during a brand change is how much of the old fluid, and how much flush water, stays in the loop. Here is the arithmetic, using one assumption we state plainly: each drain leaves a fraction r of the loop volume behind in cold plates, manifolds and low points. We use r = 10% because it matches the residual the GIGABYTE paper simulates [5]. We could not find a published measurement of drain holdup in TCS loops, and your loop could be better or worse. We also ignore the small volume change when glycol and water mix.
Case A: drain the old fluid and refill directly with the new one. The new charge is 10% old fluid. Nothing has been diluted, but you now have a 10:90 blend of two inhibitor packages.
Case B: drain, two water flushes, then fill with the new fluid. Old fluid falls to r³ = 0.1%. Water left from the second flush is r(1 - r²) = 9.9% of the loop. If the new fluid arrives at 25.0% propylene glycol by volume, the loop ends up at about 0.9 × 25.0 = 22.5%. That is below the 24% floor in OCP Rev 2.0's in-use table [1]. Even a fluid at the top of the Base Specification's 27.5% by volume range ends at about 24.75% [2], barely inside the floor. This is the over-dilution OCP's fill section warns about when residual flush water is not accounted for [1].
Case C: the 2022 OCP sequence, with a rinse in the new fluid before the final fill [3]. Old fluid falls to r⁴ = 0.01%. Water falls to r²(1 - r²) = 0.99%. Starting from 25.0%, the loop sits at about 0.99 × 25.0 = 24.75%. Rev 2.0 notes the same benefit of flushing with the heat transfer fluid itself: leftover fluid does not over-dilute the charge [1].
| Changeover method (r = 10% per drain) | Old fluid left | Flush water left | PG in loop if new fluid is 25.0 vol% |
|---|---|---|---|
| A. Drain and refill | 10% | 0% | 25.0% |
| B. Two water flushes, then fill | 0.1% | 9.9% | about 22.5% |
| C. Two water flushes, rinse with new fluid, drain, fill | 0.01% | 0.99% | about 24.75% |
Each extra drain multiplies the old-fluid share by r. If your loop holds back 20% instead of 10%, Case C leaves 0.16% old fluid and 3.8% water, for about 24.0% glycol, right at OCP's floor. Whatever method you use, Rev 2.0 says to verify concentration after fill, sampling from several points where practical once the fluid has circulated [1].
Your monitoring baseline breaks after a mix
Even when a blend is chemically benign, it undermines the tools you use to watch it. OCP Rev 2.0 points out that inhibitors change the refractive index, so the correlation between refractometer reading and glycol concentration varies from one manufacturer to another, and readings must be checked against the specific fluid's published data [1]. Its on-site testing table adds that a refractometer assumes the base fluid composition is unchanged [1]. In a blend, neither supplier's table strictly applies.
The same goes for trend data. Rev 2.0 recommends retaining a sample of fresh fluid and a start-up sample for the life of the fluid, and keeping an as-received sample from every bulk delivery for at least six months [1]. Those baselines describe one formulation. After a mix, you are comparing a new fluid against an old reference. Conductivity is the one on-site measurement OCP singles out as useful for catching fluid mixing errors, and only as a trend against a baseline [1].
What we would do
For routine top-ups, use the same product from the same supplier. If glycol concentration has drifted, follow Rev 2.0's table: below 24%, add a more concentrated fluid approved by the heat transfer fluid supplier; above 29%, add water meeting its high-purity criteria; make any adjustment with the supplier's guidance [1]. When inhibitors are depleted, Rev 2.0 says to use only additives approved by the original supplier [1].
For new racks or CDUs, ask the equipment maker in writing which fluid the hardware was filled or tested with. If it differs from your operating fluid, Rev 2.0 says to flush and fill before connection, using a protocol from your fluid supplier [1].
To change supplier, treat it as a planned changeover with a full flush, ideally timed with a flush and fill you already expect, and get sign-off from the incoming fluid supplier and from the equipment maker whose warranty depends on it. Then re-baseline: new retained samples, the new supplier's refractive index table, and a fresh conductivity reference.
If a mix has already happened, sample it from well-mixed circulating fluid, send it to a qualified lab, and share the results with both suppliers. Nothing we read says a small accidental blend demands an emergency drain. Nothing we read shows that an untested pair is safe, either.
Frequently asked questions
Can I top up a PG25 loop with water?
Only to correct a glycol concentration that has drifted above range. OCP Rev 2.0 says formulated fluids should be diluted only when concentration is above the manufacturer's range, using water that meets its high-purity criteria. Below 24% propylene glycol it calls for adding a more concentrated fluid approved by the heat transfer fluid supplier; adding water would only lower the concentration further.
If two fluids both meet the OCP PG25 Base Specification, are they interchangeable?
No. The Base Specification v1.0.0 (14 July 2026) states that compliance does not imply PG25 fluids from different suppliers are interchangeable or functionally equivalent. It sets common limits for glycol content, pH, impurities and corrosion, but it deliberately leaves inhibitor packages proprietary.
How can I tell whether fluids have been mixed in my loop?
Compare against your retained baseline samples. OCP Rev 2.0 lists electrical conductivity trending as useful for spotting large changes such as fluid mixing errors, though it does not identify the contaminant. A lab analysis of pH, reserve alkalinity, inhibitor levels and metals, shared with both fluid suppliers, is the practical way to confirm it.
Is there an OCP standard for mixing PG25 fluids?
Not yet. OCP has a PG25 Mixing workstream under its Cold Plate sub-project, but when we checked on 4 November 2026 its page said the scope would be added in the near future and listed no deliverables. Until it publishes, the operative guidance is the flush-and-fill instruction in Rev 2.0.
References
- Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Revision 2.0, Version 1.0.0. Open Compute Project, 2026-09-15. https://www.opencompute.org/wp-content/uploads/2026/10/OCP-PG25-Guidelines-V1.0.0.pdf
- Base Specification for Single-Phase Propylene Glycol-Based Cold Plate Coolants (PG 25), Version 1.0.0. Open Compute Project, 2026-07-14. https://www.opencompute.org/documents/ocp-base-specification-pg25-v1-0-0-final-pdf/
- Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Single-Phase Cold Plate-Based Liquid Cooled Racks (2022 version). Open Compute Project, 2022. https://www.opencompute.org/documents/guidelines-for-using-propylene-glycol-based-heat-transfer-fluids-in-single-phase-cold-plate-based-liquid-cooled-racks-final-pdf/
- PG25 Mixing workstream. Open Compute Project, accessed 2026-11-04. https://www.opencompute.org/?p=138357
- GIGABYTE and Castrol Co-Validate Coolant Mixing for DLC Liquid Cooling Servers (whitepaper). GIGABYTE / Giga Computing, undated, accessed 2026-11-04. https://www.gigacomputing.com/download/gigabyte-castrol-co-validate-coolant-mixing-for-dlc-liquid-cooling-whitepaper-en/
- ASTM D1384-24, Standard Test Method for Corrosion Test for Engine Coolants in Glassware (preview). ASTM International, via iTeh Standards, 2024. https://standards.iteh.ai/catalog/standards/astm/5607f7cc-bdbb-4cdf-b933-26006e1d54c6/astm-d1384-05-2019
- ASTM D2570-10, Standard Test Method for Simulated Service Corrosion Testing of Engine Coolants (preview, historical edition). ASTM International, via iTeh Standards, 2010. https://standards.iteh.ai/catalog/standards/astm/f34c5c9a-c25f-4096-beeb-5cd0dbddbd8e/astm-d2570-10
- ASTM D8040-18(2023), Standard Test Method for Corrosion Test for Heat Transfer Fluids in Glassware (preview). ASTM International, via iTeh Standards, 2023. https://standards.iteh.ai/catalog/standards/astm/5de8c9e5-be6a-438b-898b-96231a50d07e/astm-d8040-182023