Blog

How often should PG25 coolant be replaced? What the sources say

MatScienceAI · November 19, 2026 · 10 min read

Short answer

There is no fixed interval in the OCP documents. The PG25 Guidelines Rev 2.0 (September 2026) say to replace the fluid at the end of its useful life as the supplier defines it, or when it no longer meets the supplier's performance specifications, and note that suppliers typically do not guarantee fluid life. The 2022 edition's anticipated five-year life was dropped. Published supplier figures run from 2 to 8 years, each on a different basis.

Nobody publishes a fixed replacement interval for PG25 that applies to every loop, and OCP has stopped hinting at one. The 2022 OCP guidelines said an anticipated five-year fluid life could be achieved if the system was run within the document's guidelines and avoided problem materials [2]. The Rev 2.0 Guidelines, dated 15 September 2026, removed that sentence. They now say to replace the fluid at the end of its useful life as the supplier defines it, or when it no longer meets the supplier's performance specifications, and they note that suppliers typically do not guarantee the performance or lifespan of the fluid [1].

So the year figures you will find come from suppliers, and they run from 2 to 8 years. We lined them up with the basis each one gives, ran the arithmetic behind the most specific one, and set out the conditions under which Rev 2.0 says replacement may be needed.

OCP moved from a five-year expectation to a supplier-defined life

Rev 2.0 treats fluid life as something the supplier defines and the operator measures. The change from 2022 is clearest side by side.

Topic 2022 guidelines [2] Rev 2.0, September 2026 [1]
Expected life Anticipated five-year life could be achieved within the guidelines No figure. Life varies with operating temperature, system materials and fluid type
When to replace End of useful life per the supplier, or when the fluid fails the specification in the document's Table 4 End of useful life per the supplier, or when the fluid fails the supplier's own performance specifications
Guarantee Not standard policy for suppliers to guarantee performance or life span Suppliers typically do not guarantee performance or lifespan
pH out of range Replace, unless the supplier has recommended adjustments Gradual decline: adjust with supplier-recommended additives. Sudden or atypical drop: check calibration, consult the supplier; replacement may be necessary if pH is too low
Glycol out of range Replace; for larger systems, contact the supplier about adjusting Below 24%: add a supplier-approved concentrate. Above 29%: add high-purity water. Replacement may be necessary if concentration is too low, weighing project stage and fluid health

Rev 2.0 also says, just above its in-use limits table, that a deviation outside the listed ranges, to some degree, does not necessarily warrant replacement [1]. Read together, the 2022 text pointed toward draining when a reading went out of range, and Rev 2.0 points toward correcting, consulting the supplier, and replacing when correction is no longer sensible. The July 2026 PG25 Base Specification, which sets requirements for new fluid, lists longer system life among its aims, but we found no service-life requirement in it [3]. OCP's Modular TCS document (Rev 1, August 2025) takes the same line as Rev 2.0: boost inhibitors or adjust pH when out of range, and reserve a full drain, flush and refill for severe contamination or fluid breakdown [4].

Our comparison of the Base Specification and Rev 2.0 covers the in-use limits in full.

Published life figures, and the basis behind each

Apart from the withdrawn 2022 OCP figure, every year figure we found came from a supplier. Shell is the only one that footnotes its basis.

Source Figure published Conditions stated Basis given
Shell, DLC Fluid S3 page [5] Expected life of 6+ years None for the data center loop Footnote: performance of a product with similar chemistry in automotive use, described as higher temperature and pressure
Recochem, OAT PG-25 Computer Coolant data sheet v3.2, Jan 2024 [6] Up to 8 years in a computer coolant application Maintained with extender (booster) per the equipment maker's directions Not stated
Alliance Chemical, Apr 2026 [7] OAT 5 to 7 years nominal; nitrited OAT 4 to 5; silicated hybrid OAT 3 to 5 Properly maintained OAT in controlled environments Not stated for the ranges
Alliance Chemical, same article [7] OAT compressed to 2 to 3 years 85 kW rack of 32 B200 GPUs, 20 L/min per server node Author's estimate from an oxidation-rate rule of thumb (worked through below)
Alliance Chemical, Apr 2026 [8] Typical calendar practice: 3 years for high-density direct liquid cooling, 5 years for lower-stress glycol loops Calendar-based replacement, described as common practice Not stated
Alliance Chemical, same article [8] With predictive inhibitor dosing: 4 to 5 years high-density, 6 to 7 years moderate stress Inline sensors, quarterly lab analysis, targeted inhibitor additions Not stated
Alliance Chemical, Aug 2025 [9] OAT lifespan 5 to 8 years in its inhibitor summary, but plan an OAT change-out every 5 to 7 years in its maintenance list; hybrid OAT may need it at 4 to 5 years Properly maintained closed loop; annual lab analysis and quarterly on-site checks Not stated
Tetra Tech green paper, May 2025 [10] No fluid life given Quarterly chemical analysis; annually, flush and replace aging components if necessary Not applicable
Interstate Chemical and Crystal Clean data sheets [11][12] No year figure Both offer inhibitor additions when analysis shows they are needed Not applicable

Three things stand out. First, the figures are not measuring the same thing. Shell's 6+ years rests on automotive experience with similar chemistry [5], Recochem's 8 years assumes extender has been added along the way [6], and Alliance's 4 to 7 years in one article assume predictive dosing [8]. A figure that includes re-inhibiting is a different promise from one that does not.

Second, the Recochem sheet gives the same 8 years as the shelf life of sealed product stored dry and out of direct sunlight [6]. Do not confuse shelf life with life in a running loop.

Third, one publisher's figures alone run from 2 to 8 years [7][8][9]. Alliance's 2 to 3 year figure for one high-density case and its 5 to 7 or 5 to 8 year figures for OAT apply to different conditions, which shows how much conditions matter compared with the label on the drum. The 2025 guide's own 5 to 7 and 5 to 8 year OAT figures do not reconcile, and the guide does not explain the difference [9].

Worked check: what a doubling-per-10 °C rule implies

Temperature is the variable Alliance's most specific estimate turns on, together with flow rate, and the arithmetic shows why a single year figure cannot cover every loop. Alliance's April 2026 article states that the oxidation rate of OAT inhibitors roughly doubles for every 10 °C rise, and that at a 70 °C cold-plate wall temperature against a 45 °C reference, the rate at the metal surface is 4 to 6 times the reference [7]. The arithmetic below is ours.

  • The rule gives 2^(25/10) = 2^2.5 = 5.7 times for a 25 °C rise, inside Alliance's 4 to 6 range.
  • If the whole charge aged 5.7 times faster, a 5 to 7 year life would shrink to 5 ÷ 5.7 = 0.9 years and 7 ÷ 5.7 = 1.2 years.
  • Alliance's own estimate for that rack is 2 to 3 years [7]. Going from 5 to 7 years down to 2 to 3 years is a factor of 5 ÷ 3 = 1.7 at the gentlest pairing and 7 ÷ 2 = 3.5 at the harshest. Under the same rule, that equals an effective temperature rise of 10 × log2(1.7) = 7 °C to 10 × log2(3.5) = 18 °C, not 25 °C.

That gap makes sense physically, since the fluid spends only part of each circuit in the hot layer next to the cold-plate wall. It also shows the 2 to 3 year figure is not a straight application of the rule. The article gives no test data behind it, and we could not find any [7].

The same rule shows how wide the range can be. Rev 2.0 gives the typical operating temperature of closed-loop systems as 17 to 66 °C [1]. Across those 49 °C, a doubling-per-10 °C rule gives 2^4.9, about a 30-fold difference in reaction rate from one end of the range to the other. Real fluids will not follow a textbook rule that neatly, but it is a reason to ask any supplier quoting a life in years what temperature they assumed. Rev 2.0 lists operating temperature, system materials and fluid type as the key factors in fluid life, without ranking them [1].

Why PG25 wears out: acids from the glycol, and inhibitor used up

Two things age a PG25 charge: the glycol slowly oxidizes into acids, and the corrosion inhibitors are consumed as they protect metal. Rev 2.0 says inhibitors form a protective layer that consumes them gradually, and that concentrations can fall through use, system aging or fluid degradation [1].

On the glycol side, the clearest primary source we found is old and from solar heating, not data centers. A 1983 NIST study of heated glycol solutions found that propylene glycol degraded mainly to lactic acid, that metallic copper increased the amount of degradation products, and that aluminum produced only slightly more degradation than no metal but relatively large amounts of formic acid [13]. We read the abstract only. Alliance says most enterprise GPU cold plates are copper [7], and Rev 2.0 asks for dissolved copper to be tracked in service [1].

Oxygen speeds this up. Tetra Tech's design guide says exposure to oxygen triggers glycol oxidation and acidic byproducts, that oxidized PG25 can drop in pH, and recommends a fully sealed loop for that reason [10]. Air ingress is something an operator controls, so in our view it is one of the first things to check when a loop ages faster than its siblings.

The readings that signal replacement in Rev 2.0

Rev 2.0 does not give a single "replace now" number. It gives in-use limits and says replacement may be necessary for three conditions [1]:

Parameter Rev 2.0 in-use limit Rev 2.0 remediation
pH 8.0 to 10.5 for conventional (IAT) fluids; 6.5 to 9.5 for OAT or hybrid Gradual decline: supplier-recommended additives. Sudden drop: recalibrate, consult supplier. Replacement may be necessary if too low
Glycol concentration 24 to 29% by volume for PG25 Add supplier-approved concentrate below 24%. Replacement may be necessary if too low
Appearance Clear and free of particulates Lab analysis, sidestream filtration. Replacement may be necessary after severe contamination
Reserve alkalinity Above 4 mL (ASTM D1121, 10 mL sample) for conventional fluids; for OAT, no limit, report the value only Consult supplier; supplier-approved additives
Copper, iron Below 3 ppm each Above 5 ppm: monitor more often, consult supplier
Chloride, sulfate Below 25 ppm each Watch for corrosion; consult supplier above 50 ppm (chloride) or 100 ppm (sulfate)

Rev 2.0 marks these remediations as examples and defers to the fluid manufacturer [1]. A pH reading should always be compared with the loop's own baseline, which is why the commissioning sample matters. Our article on how often to test PG25 sets out the sampling schedule that produces the trend.

Suppliers do not all read the same signals the same way. Alliance's 2025 guide treats a pH drop of more than 1.0 unit from baseline as a reason for an immediate full change-out rather than a top-up [9], while Rev 2.0 asks first whether the drop is gradual or sudden and whether the probe is calibrated [1]. Ask your supplier which rule they apply before the first out-of-range result arrives.

Topping up inhibitor: only with the original supplier's additive

Two of the longer figures, Recochem's 8 years and Alliance's predictive-dosing figures, assume re-inhibiting, and Rev 2.0 limits who may supply the additive. When analysis shows depletion, it says to use only additives approved by the original fluid supplier, and warns that unapproved additives or overdosing can cause precipitation, reduced heat transfer and faster corrosion [1]. Interstate Chemical describes inhibitors added at first fill and again for remediation when required [11]. Crystal Clean offers a concentrated booster to restore inhibitor content based on lab testing [12]. Recochem ties its 8-year figure to extender use [6].

The practical point for a buyer: a quoted life that assumes re-inhibiting is only reachable if the additive, the lab support and the dosing method are part of the supply agreement. In our reading, because Rev 2.0 restricts additives to those approved by the original fluid supplier [1], changing to another supplier's product later is a flush and fill, not a top-up, as we covered in can you mix PG25 coolants.

How we would plan for replacement

Budget for a change-out at the supplier's written figure, and get the basis in writing too: the temperature, materials and maintenance it assumes, and whether re-inhibiting is included. Then let the trended lab results decide the actual date. If the supplier's figure and the chemistry disagree, the chemistry wins, which is what Rev 2.0's "no longer meets the performance specifications" clause means in practice [1].

Look at the IT refresh calendar as well. OCP's Modular TCS document describes disconnecting a liquid-cooled rack as infrequent, typically at a major IT refresh every 3 to 7 years or longer [4]. A change-out planned around a refresh can share the drain and recommissioning work with it.

When the fluid comes out, Rev 2.0 says not to dump new or used fluid into sewers, onto the ground or into water, and notes that most used propylene glycol fluids can go to commercial glycol recyclers [1]. Check the SDS and local rules before the drain is scheduled.

Frequently asked questions

Does OCP set a replacement interval for PG25?

No. The PG25 Guidelines Rev 2.0 (15 September 2026) leave the interval to the fluid supplier and add replacement when the fluid no longer meets the supplier's performance specifications. The 2022 edition said an anticipated five-year life could be achieved in a system run within its guidelines, but that sentence is not in Rev 2.0. We found no service-life requirement in the July 2026 PG25 Base Specification either.

Can PG25 life be extended by adding inhibitor?

Several suppliers sell a booster or re-inhibiting additive for this, and one datasheet ties its up-to-8-year figure to using an extender. OCP Rev 2.0 says to restore depleted inhibitors only with additives approved by the original fluid supplier, because unapproved additives or overdosing can cause precipitation, fouling and faster corrosion. Rev 2.0 ties the addition to analysis showing depletion, so dose from a lab result.

Does a pH drop mean the PG25 has to be replaced?

Not automatically under OCP Rev 2.0. A gradual decline can be corrected with supplier-recommended additives, while a sudden or atypical drop calls for checking the pH probe calibration and then consulting the supplier, and replacement may be necessary if pH is too low. One supplier blog is stricter and calls for a full change-out after a drop of more than 1.0 pH unit from baseline.

What should be done with PG25 after it is drained?

OCP Rev 2.0 says not to dump new or used fluid into sewers, onto the ground or into any body of water, and makes the waste generator responsible for waste characterization and legal compliance. It notes that most used propylene glycol fluids can go to commercial glycol recyclers as feedstock. Check the SDS and local rules before planning the drain.

References

  1. Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Revision 2.0, Version 1.0.0. Open Compute Project, 2026-09-15. https://www.opencompute.org/wp-content/uploads/2026/10/OCP-PG25-Guidelines-V1.0.0.pdf
  2. Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Single-Phase Cold Plate-Based Liquid Cooled Racks (2022 version). Open Compute Project, 2022. https://www.opencompute.org/documents/guidelines-for-using-propylene-glycol-based-heat-transfer-fluids-in-single-phase-cold-plate-based-liquid-cooled-racks-final-pdf/
  3. Base Specification for Single-Phase Propylene Glycol-Based Cold Plate Coolants (PG 25), Version 1.0.0. Open Compute Project, 2026-07-14. https://www.opencompute.org/documents/ocp-base-specification-pg25-v1-0-0-final-pdf/
  4. Modular Technology Cooling System for Cloud Scale: Design and Delivery of Liquid to Rack Distribution Systems, Rev 1. Open Compute Project, 2025-08-25. https://www.opencompute.org/documents/ocp-modular-tcs-rev-1-final-2025-pdf
  5. Shell DLC Fluid S3 product page. Shell, 2026-09-26 (page last updated). https://www.shell.com/business-customers/industrial-lubricants-and-specialty-fluids-for-business/liquid-cooling-fluids/direct-liquid-cooling.html
  6. OAT PG-25 Computer Coolant, Product Technical Data Sheet, Version 3.2. Recochem (distributor-hosted copy), 2024-01-26. https://prostech.vn/wp-content/uploads/2025/03/OAT-PG-25-Computer-Coolant.pdf
  7. OAT vs NOAT vs HOAT Inhibitor Chemistry for Data Center Cooling. Alliance Chemical (Andre Taki), 2026-04-27. https://alliancechemical.com/blogs/articles/oat-vs-noat-vs-hoat-inhibitor-data-center
  8. Inhibitor Depletion Lifecycle and the Case for Coolant-as-a-Service. Alliance Chemical (Andre Taki), 2026-04-27. https://alliancechemical.com/blogs/articles/inhibitor-depletion-lifecycle-coolant-as-a-service
  9. The Unseen Chemistry of AI: The Definitive Guide to Data Center Coolants & Chemicals. Alliance Chemical (Andre Taki), 2025-08-29. https://alliancechemical.com/blogs/articles/the-unseen-chemistry-of-ai-the-definitive-guide-to-data-center-cooling-chemicals
  10. Practical Design Guide to Optimizing Data Center Direct-to-Chip Liquid Cooling with PG 25, Revision 1.1. Tetra Tech (Sam Khalilieh), 2025-05-15. https://www.tetratech.com/wp-content/uploads/2025/05/TTHPBG-PG25-Data-Centre-White-Paper_1.1.pdf
  11. INTERCOOL DC-300 25% Technical Data Sheet. Interstate Chemical, undated, accessed 2026-11-19. https://interstatechemical.com/assets/docs/INTERCOOL-DC-300-25-Tech-Bulletin.pdf
  12. PGDC Propylene Glycol-Based Direct-to-Chip Coolant data sheet. Crystal Clean, undated, accessed 2026-11-19. https://www.crystal-clean.com/wp-content/uploads/2026/05/PGDC-Data-Sheet.pdf
  13. Determination of Acidic Degradation Products in Aqueous Ethylene Glycol and Propylene Glycol Solutions Using Ion Chromatography (Solar Energy Materials 9, 267-279). Rossiter, Brown and Godette, National Institute of Standards and Technology (abstract), 1983. https://firedoc.nist.gov/article/2XgzXYQBWEcjUZEYfzaJ