Coolant reserve alkalinity: what D1121 measures and why OAT differs
MatScienceAI · November 23, 2026 · 11 min read
Short answer
Coolant reserve alkalinity is the millilitres of 0.100 N HCl that take a 10 mL sample to pH 5.5 (ASTM D1121). For conventional fluids, OCP's PG25 Guidelines Rev 2.0 give above 6 mL as typical when new and above 4 mL as the in-use limit. For OAT fluids it asks only for the value. The pH 5.5 endpoint was set for borate and phosphate buffers, and two OAT-type PG25 fluids list 3.0 and 1.4 mL.
Reserve alkalinity is a titration result: the millilitres of 0.100 N hydrochloric acid it takes to bring a 10 mL coolant sample down to pH 5.5 [4]. For conventional inhibitor packages, OCP's PG25 Guidelines Revision 2.0 (dated September 2026) give a typical new-fluid value above 6 mL and an in-use limit above 4 mL. For OAT packages they set no number and ask only for the value to be reported [1]. That split matters in practice. Of the five PG25 products whose public data we compare below, Savita (OAT) and Clariant (hybrid OAT) list 3.0 and 1.4 mL, and Recochem's OAT PG-25, described as organic additive technology, specifies a 1.5 mL minimum [10][11][12]. Both listed values, and Recochem's minimum (which sets no upper bound), sit under the 4 mL that applies to conventional fluids in service.
D1121 counts acid down to pH 5.5, a point chosen for borate and phosphate buffers
The method dilutes a 10 mL sample to about 100 mL with water and titrates it potentiometrically with 0.100 N hydrochloric acid to pH 5.5, reporting the acid used to the nearest 0.1 mL [4]. Rev 2.0 specifies the 10 mL sample as ready-to-use (pre-diluted) fluid, so a PG25 result describes the fluid as it sits in the loop, not the concentrate [1].
The endpoint has a history. In its account of the term's origin, ASTM describes glycol coolants containing triethanolamine, whose neutralization curve was steepest near pH 5.0. When borate and phosphate buffers came into use after it, the 5.5 endpoint was adopted to match them, since their own end point lies near that pH [4]. The Texaco patent discussed below places borate neutralization earlier, by about pH 7 [5]; the two sources describe different titrations and do not agree exactly. In our reading, that choice of endpoint is why OAT fluids read low (see below).
ASTM also states what the number does not tell you. The same section says the term is sometimes misused as a measure of coolant quality, that inhibitors contributing little reserve alkalinity can still protect certain metals well, and that the number cannot be relied on to show either how well a solution prevents corrosion or how much life it has left [4]. What it does measure is the alkaline buffer that neutralizes acid from residual acid cleaners, exhaust gas leaks (an engine problem, absent in a TCS loop) and oxidation of the glycol [4].
A note on editions: Rev 2.0 cites D1121-25 [1], and the 2022 guidelines cited D1121-11(2020) [3]. We read the public significance section of the 2020 edition; the 2025 text is paywalled and we could not check whether that section changed.
To put the result in chemical units: 1 mL of 0.100 N acid is 0.1 mmol, and dividing by the 10 mL sample gives 10 mmol of acid per litre of coolant for every 1 mL of reserve alkalinity. OCP's 6 mL and 4 mL are therefore 60 and 40 mmol/L.
OCP's reserve alkalinity numbers, 2022 to 2026
Rev 2.0 added the OAT exception and raised the new-fluid figure; the Base Specification sets no value at all.
| Document | New fluid (typical) | In-use fluid | Sample |
|---|---|---|---|
| 2022 guidelines [3] | Above 4 mL ("unadjusted"), all fluids | Above 4 mL, all fluids | Diluted fluid (typical table); fluid as-is (in use) |
| Base Specification v1.0.0, July 2026 [2] | No limit; qualified labs must be able to run D1121; test strips not acceptable | No limit | Not stated |
| Rev 2.0, September 2026 [1] | Above 6 mL for conventional; report only for OAT | Above 4 mL for conventional; report only for OAT | 10 mL of ready-to-use fluid |
The 2022 guidelines already noted that pH may be lower with organic acid technology, but they applied the same reserve alkalinity floor to every fluid [3]. We could not find a definition of "unadjusted" anywhere in the 2022 text. The Base Specification requires the qualified labs that fluid manufacturers must offer to be able to run reserve alkalinity, and it lists corrosion inhibitors separately, to be tested by ion chromatography or HPLC per the supplier's recommendations [2]. Its minimum certificate of analysis covers glycol concentration (or refractive index) and pH, not reserve alkalinity [2], so a delivery can arrive with no RA figure unless the purchase contract asks for one.
Rev 2.0's in-use table says to consult the supplier if reserve alkalinity is out of range, and that additives to raise it may be available but should only go in under the supplier's guidance [1]. Its glossary treats RA as a test-method-specific measure of how much acid the fluid can absorb, and says to judge it against the inhibitor chemistry and the supplier's advice [1]. In its section on testing fluid after elastomer exposure tests, it lists inhibitor concentration and reserve alkalinity as alternatives within one item [1]. We read that as two routes to the same question.
One gap. The in-use pH row in Rev 2.0 groups hybrid packages with OAT (6.5 to 9.5 in service) [1], but the reserve alkalinity row names only conventional and OAT-based technologies [1]. A hybrid fluid is not placed in either. Ask the supplier which row it belongs to, in writing.
Why an OAT fluid can read low: carboxylates take most of their acid below pH 5.5
Rev 2.0 defines OAT as corrosion inhibition based primarily on organic acids [1], which sit in the fluid as carboxylate salts. Texaco's patent on a field titration for coolants and heat-exchange fluids, tested on its own engine coolants, describes how they behave when acid is added. A fully carboxylate coolant shows a first end point (the patent calls it an equilibrium point) near pH 7.0 with only a small amount of acid consumed, and the carboxylates are converted to their acids between that point and a second one at pH 3. Borate and silicate inhibitors, by contrast, are neutralized before the first point. A hybrid coolant containing borate, silicate, benzoate and carboxylates already takes considerable acid at the first point [5].
The patent gives a pKa of 4.5 for typical aliphatic organic acids [5]. Taking that figure at face value, the Henderson-Hasselbalch ratio at pH 5.5 is 10^(5.5 − 4.5) = 10 carboxylate ions for every protonated acid, so only 1 in 11, about 9%, of a carboxylate inhibitor has taken up acid when D1121 stops. Real inhibitor acids each have their own pKa and the 25% glycol matrix may shift them, so read this as an order of magnitude. This is our reading, not OCP's stated reason (Rev 2.0 says only that reserve alkalinity depends on the inhibitor formulation and should be read against the inhibitor technology [1]), but it fits: D1121 ends before most of a carboxylate package's acid uptake has happened.
That fits the case ASTM describes, inhibitors that give little reserve alkalinity but can protect certain metals very well [4]. ASTM adds that such inhibitors do little to neutralize acid contamination [4], which is the trade-off. A low RA in an OAT fluid is therefore no surprise. In our reading, it also means the RA number cannot reliably tell you how much carboxylate is left. For that, the Base Specification's route is a direct inhibitor measurement by IC or HPLC [2], and inhibitor concentration is on Rev 2.0's minimum annual lab panel [1].
Published PG25 datasheets: the split in numbers
We collected every reserve alkalinity value we could find in public product data for PG25 data-center fluids and converted each to mmol/L. These are suppliers' own figures; we have not tested any of the fluids.
| Fluid (publisher) | Inhibitor technology as stated | Reserve alkalinity, D1121 | mmol/L | Status of the figure |
|---|---|---|---|---|
| INTERCOOL DC-300 25% (Interstate Chemical) [9] | Organic and inorganic inhibitors; pH 8.0 to 10.5 | Above 6.0 mL | Above 60 | Typical, not a specification |
| QuantiCool PG 25 (Savita) [10] | OAT; no nitrites, phosphates, silicates or amines | 3.0 mL | 30 | Listed as result |
| OAT PG-25 Computer Coolant (Recochem) [12] | Proprietary organic additive technology; no 2-EHA, borate, nitrite, amine or silicate | 1.5 mL minimum | At least 15 | Minimum (sales specification) |
| Antifrogen PG 25 (Clariant) [11] | Hybrid OAT | 1.4 mL (0.1 M HCl) | 14 (if measured as supplied) | Listed value, not marked typical or specification; sample dilution not stated |
| PG25 with OAT inhibitor (Alliance Chemical) [14] | Nitrite-containing hybrid organic acid | Reported on lot certificate | Not given | No fixed value |
Three things stand out. First, Savita lists 3.0 mL for its OAT fluid and Clariant 1.4 mL for its hybrid-OAT fluid [10][11]. Recochem, whose datasheet describes an organic additive technology rather than naming organic acids, specifies a minimum of 1.5 mL [12], which says nothing about the upper end. Against Rev 2.0's conventional in-use figure of 4 mL, both listed values read low (Clariant does not state the sample dilution), which is why the "to report" wording matters. Interstate's fluid, with organic and inorganic inhibitors and not described as OAT or hybrid, lists above 6.0 mL [9]. The same Savita document gives 5.36 mL for its 50% ethylene glycol OAT battery coolant [10]. That is a different product (ethylene glycol, 50%, battery service) outside PG25, so the two numbers are not comparable.
Second, a product name alone does not settle which row applies. Alliance's product name says OAT inhibitor, and its datasheet describes the package as a nitrite-containing hybrid organic acid with sodium nitrite, triethanolamine, sodium benzoate and sodium molybdate, and reports RA per lot [14]. A fluid like that may sit between the two OCP rows, and we have no RA data for it. Clariant's page gives pH (about 8.8) measured at 33% v/v in deionized water but does not say what dilution the RA was measured on [11], so it cannot be compared directly with Rev 2.0's ready-to-use basis.
Third, Alliance Chemical's blog gives 8 to 15 mL for new heavy-duty industrial coolant [13]. None of the values listed above falls in that range (Interstate gives only a lower bound of 6.0 mL), and the blog names no product or source, so we would not use it as a benchmark for a PG25 loop.
Worked example: what 2 mL of reserve alkalinity buys
Between a conventional fluid delivered at exactly 6 mL and the 4 mL in-use floor lie 2 mL, or 20 mmol of acid-neutralizing capacity per litre (2 × 10 mmol/L).
Which acid? Rossiter and colleagues, in a study listed in NIST's publication record, studying glycol solutions for solar collectors, analysed thermally degraded samples by ion chromatography and found lactic acid to be the main acid formed from propylene glycol. Metallic copper increased degradation, and with aluminum present formic acid became prominent [6]. That work was not on TCS loops, so we are carrying its finding across. Lactic acid has a molar mass of 90.08 g/mol [7] and a pKa of 3.86 at 20 °C [8], so at pH 5.5 about 98% of it is dissociated (1 / (1 + 10^(3.86 − 5.5))). To a first approximation, each millimole of lactic acid uses one millimole of reserve.
- 20 mmol/L × 90.08 mg/mmol = about 1,800 mg of lactic acid per litre
- In a 1,000 L (264 US gal) TCS loop: 20 mol, or about 1.8 kg of lactic acid
So the margin between OCP's typical new figure and its in-use figure is about 1.8 kg of lactic acid in a 1,000 L loop, and it is not a measure of time. The NIST abstract we read does not give test temperatures or rates [6], and we found no public PG25 data linking acid formation rate to loop temperature, so we cannot turn 1.8 kg into months.
The calculation also assumes all of the drop comes from acid. Two other things lower the number. Rev 2.0 says corrosion inhibitors form a protective layer on metal surfaces and are consumed gradually as they do [1]. That consumption does not need acid, and where the consumed inhibitor contributes to RA it will lower the number (our inference). Dilution is the other one, and it can mislead. If a loop at 27% glycol reading 4.4 mL is topped up with water until it reads 24%, still inside Rev 2.0's 24 to 29% in-use window [1], and the inhibitor is diluted in the same proportion, the RA falls to 4.4 × 24/27 = 3.9 mL. The fluid has crossed the 4 mL line without any chemistry happening. Alliance's own datasheet notes that further dilution lowers inhibitor concentration along with freeze protection [14]. Our suggestion: read every RA result next to the glycol result from the same sample, and scale it to the commissioning glycol level before calling a trend.
Trend against your own baseline, then ask about the number that matters
The reference point that means most is your own fluid's value at start-up. Rev 2.0 wants a sample from every loop taken in its first one to three days of running and kept until the fluid is replaced [1]. For a conventional fluid, Rev 2.0's absolute floor of 4 mL then sits alongside the trend, though Rev 2.0 also says a result outside its ranges need not mean the fluid must be replaced [1]. Alliance's blog proposes a relative rule instead, with a change-out to be scheduled once RA falls to between 25% and 50% of the commissioning baseline. Its depletion table is presented as data from one monitored propylene glycol loop (40 °C, 30% glycol), offered as an illustration, with no site, product or dataset identified [13]. For a fluid delivered at 6 mL, 50% of baseline is 3 mL, below OCP's floor, so the two rules give different answers for the same sample. We would use OCP's floor for conventional fluids and treat percentage rules as a supplier conversation.
For an OAT fluid, reserve alkalinity stays on Rev 2.0's minimum annual lab panel [1], but do not pay for extra RA tests in the belief that they track inhibitor life. Ask the supplier three things: the new-fluid RA on the certificate of analysis for your lot, the parameter they use to judge inhibitor depletion (the Base Specification's lab list includes direct inhibitor testing by IC or HPLC [2]), and the value at which they would recommend a top-up with their own additive, since Rev 2.0 only allows supplier-approved additives [1]. Put the answers in the supply agreement. Our articles on how often to test PG25 and the full OCP limit tables cover the sampling calendar and the other in-use limits, and the replacement article covers what happens when inhibitor runs out. If a loop has ever been topped up with a different product, the baseline itself is in doubt; see mixing PG25 coolants.
Frequently asked questions
What is a good reserve alkalinity for a PG25 coolant?
For a conventional (IAT) fluid, OCP's PG25 Guidelines Rev 2.0 give more than 6 mL as typical for new fluid and more than 4 mL as the in-use limit, both by ASTM D1121 on a 10 mL sample of ready-to-use fluid. For OAT fluids OCP sets no number and asks for the value to be reported. In both cases the useful reference is your own fluid's value at commissioning, from a retained baseline sample.
My OAT coolant reads 2 mL reserve alkalinity. Is it failing?
Not on that number alone. Published PG25 data list 3.0 mL for one OAT fluid and 1.4 mL for one hybrid-OAT fluid, both below the 4 mL in-use limit OCP applies to conventional fluids. Compare the result with the fluid's own new value and ask the supplier which parameter tracks inhibitor health; OCP's Base Specification lists direct inhibitor testing by ion chromatography or HPLC.
Is reserve alkalinity the same as pH?
No. pH is the hydrogen-ion activity at one moment; reserve alkalinity is how much acid the fluid takes up before it falls to pH 5.5. ASTM D1121 says borate and phosphate buffers keep pH stable as acid is added, so, by our reading, pH can stay normal while the reserve is being used up. The standard also notes that the name is imprecise, because the word normally implies a pH above 7, yet the titration ends at 5.5.
Can reserve alkalinity be measured with test strips?
OCP's PG25 Base Specification says test strips are not an acceptable method for reserve alkalinity in the qualified labs that fluid manufacturers must offer, because they are not accurate enough. ASTM D1121 is a potentiometric titration with a pH electrode, reported to the nearest 0.1 mL.
References
- Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Revision 2.0, Version 1.0.0. Open Compute Project, 2026-09. https://www.opencompute.org/wp-content/uploads/2026/10/OCP-PG25-Guidelines-V1.0.0.pdf
- Base Specification for Single-Phase Propylene Glycol-Based Fluids (PG 25), Version 1.0.0. Open Compute Project, 2026-07-14. https://www.opencompute.org/documents/ocp-base-specification-pg25-v1-0-0-final-pdf/
- Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Single-Phase Cold Plate-Based Liquid Cooled Racks (2022 version). Open Compute Project, 2022. https://www.opencompute.org/documents/guidelines-for-using-propylene-glycol-based-heat-transfer-fluids-in-single-phase-cold-plate-based-liquid-cooled-racks-final-pdf/
- ASTM D1121-11(2020) Standard Test Method for Reserve Alkalinity of Engine Coolants and Antirusts (catalog abstract and significance section). ASTM International, via iTeh Standards, 2020. https://standards.iteh.ai/catalog/standards/astm/ed8342f1-f571-4f6a-8cb1-0aee869920ca/astm-d1121-11
- US 6,495,372 B1: Field test apparatus and method for analysis of coolants and heat-exchange fluids. Texaco Inc. (Maes, Roose, Van Kenhove), via Google Patents, 2002-12-17. https://patents.google.com/patent/US6495372
- Determination of acidic degradation products in aqueous ethylene glycol and propylene glycol solutions using ion chromatography (Solar Energy Materials 9, 267-279). Rossiter, Brown and Godette, NIST record, 1983. https://firedoc.nist.gov/article/2XgzXYQBWEcjUZEYfzaJ
- Lactic acid (CID 612): computed properties. PubChem, US National Library of Medicine, accessed 2026-11-23. https://pubchem.ncbi.nlm.nih.gov/rest/pug/compound/cid/612/property/MolecularWeight,IUPACName,Title/JSON
- Lactic acid (CID 612): dissociation constants. PubChem, US National Library of Medicine, accessed 2026-11-23. https://pubchem.ncbi.nlm.nih.gov/rest/pug_view/data/compound/612/JSON?heading=Dissociation+Constants
- Technical Data Sheet: INTERCOOL DC-300 25% Direct-to-Chip Liquid Cooling Fluid. Interstate Chemical Co., undated, accessed 2026-11-23. https://interstatechemical.com/assets/docs/INTERCOOL-DC-300-25-Tech-Bulletin.pdf
- QuantiCool glycol-based coolants (EG 50 and PG 25 technical data). Savita Oil Technologies, 2026. https://savita.com/wp-content/uploads/2026/02/Quanticool-DLC.pdf
- Antifrogen PG 25 product page. Clariant, page modified 2026-10-02. https://www.clariant.com/en/Solutions/Products/2026/04/09/10/13/ANTIFROGEN-PG-25
- Product Technical Data Sheet: OAT PG-25 Computer Coolant, Version 3.2. Recochem (copy hosted by distributor Prostech), 2024-01-26. https://prostech.vn/wp-content/uploads/2025/03/OAT-PG-25-Computer-Coolant.pdf
- Reserve alkalinity testing cadence (ASTM D1121) for data center coolant loops. Alliance Chemical (Andre Taki), 2026-04-27. https://alliancechemical.com/blogs/articles/reserve-alkalinity-testing-cadence-astm-d1121
- Technical Data Sheet: Inhibited Propylene Glycol 25/75 with OAT Inhibitor, Data Center Coolant, Version 1.4. Alliance Chemical, 2026-11-04. https://alliancechemical.com/cdn/shop/files/inhibited-propylene-glycol-25-75-with-oat-inhibitor-data-center-coolant_8fb201cb-6568-4ea9-899d-1f1be5f5a0a1.pdf